Simplex 4090-9001 Supervised Class B monitoring of normally open, dry contacts
Total wiring distance from IAM to supervision resistor(s) of up to 500 ft (152 m)
Monitored connection is compatible with Simplex® 2081-9044 Overvoltage Protectors for outdoor wiring or electrically noisy applications For use in indoor locations up to 158° F (70° C) such as attic spaces or similar applications For use with following Simplex control panels:
Model Series 4007ES, 4008, 4010, 4010ES, and 4100ES fire alarm control panels for IDNet communications
Model Series 4100/4100U/4100ES, 4120, 4020, and 2120 Communicating Device Transponders (CDTs) equipped with MAPNET II communications Model 4090-9001:
Enclosed design minimizes dust infiltration
Mounts in standard single gang electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers are available to allow LED to be viewed after installation (requires mounting bracket, ordered separately) Model 4090-9051:
Encapsulated design for extended exposure to high humidity (LED is not present on this model)
Color coded 18 AWG leads for wiring IDNet communications provides current limited monitoring:
Provides monitoring of tamper switch (supervisory) and waterflow switch (alarm) on same circuit using one point
Available with IDNet communications only Multiple operation modes are available and are selectable at the control panel:
Contact closure status can be tracked