General
The NFS2-3030 is an intelligent Fire Alarm Control Panel (FACP)
designed for medium- to large-scale facilities. Fire emergency detection and evacuation are extremely critical to life safety, and the
NFS2-3030 is ideally suited for these applications. The NFS2-3030
is part of the ONYX® Series of products from NOTIFIER. The NFS2-
3030 is ideal for virtually any application because it features a modular design that is configured per project requirements. With one to
ten Signaling Line Circuits (SLCs), the NFS2-3030 supports up to
3,180 intelligent addressable devices.
Information is critical to fire evacuation personnel, and the NFS2-
3030’s large 640-character Liquid Crystal Display (LCD) presents
vital information to operators concerning a fire situation, fire progression, and evacuation details.
A host of other options are available, including single- or multi-channel voice; firefighter’s telephone; LED, LCD, or PC-based graphic
annunciators; networking; advanced detection products for challenging environments; wireless fire protection; and many additional
options.
ONYX® Series panels integrate with the Connected Life Safety Services (CLSS) platform through the CLSS Gateway, providing
connectivity to central station, cloud, and mobile applications. (See
HON-62034.) This cloud-based functionality provides reliable protection and remote monitoring of the system, reduced manual data
entry, and reporting.
Features
• Certified for seismic applications when used with the appropriate
seismic mounting kit.
• Approved for Marine applications when a marine-listed version is
used with marine-listed compatible equipment. See DN-60688.
• Complies with UL 2572 Mass Notification Systems (NFS2-3030
version 20 or higher).
• One to ten isolated intelligent Signaling Line Circuits (SLC) Class
A, B, or X.
• Wireless fire protection using SWIFT Smart Wireless Integrated
Fire Technology. See DN-60820.
• Up to 159 detectors and 159 modules per SLC; 318 devices per
loop/3,180 per FACP or network node.
– Detectors can be any mix of photo, thermal, or multi-sensor;
wireless detectors are available for use with the FWSG(A).
– Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay;
wireless modules are available for use with the FWSG(A).
• Large 16 line, 640 character LCD backlit display or use displayless as a network node.
• Network options:
– High-speed network for up to 200 nodes (N16e/x, NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA).
– Standard network for up to 103 nodes (N16e/x, NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP300/400, AFP-1010, and AM2020). Up to 54 nodes when DVCEM is used in network paging.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• VeriFire® Tools online/offline program option.
• With built-in Degraded Mode operation, the system is capable of
general alarm if a fire alarm condition is present even if the central processing unit (CPU) fails.
• Weekly Occupancy Schedules allow changing sensitivity by time
of day and day of week.
• EIA-485 annunciators, including custom graphics.
• History file with 4000-event capacity in nonvolatile memory, plus
separate 1000-event alarm-only file.
• Advanced history filters allow sorting by event, time, date, or
address.
• Alarm Verification selection per point, with automatic counter.
• Autoprogramming and Walk Test reports.
• Multiple central station communication options:
– Standard UDACT
– Internet
– Internet/GSM
• Positive Alarm Sequence (PAS) Presignal.
• Silence Inhibit and Auto Silence timer options.
• Optional cloud connectivity for remote off site monitoring through
CLSS (see HON-62034)
• Monitor multiple buildings through one off-campus central station,
and report through the CLSS Gateway
• Optional remote programing through CLSS
• Field-programmable on panel or on PC, with VeriFire Tools program, also check, compare.
• Non-alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via monitor modules.
• Up to 1000 powerful Boolean logic equations.
• Supports SCS Series smoke control system in both HVAC and
FSCS modes.
• FM6320 approved Gas Detection System with FMM-4-20 module
and any FM listed gas detector.
• EIA-232 printer port.
• EIA-485 annunciator port.