General
FMM-1(A) is a standard-sized module (typically mounts to a
4″ [10.16 cm] square box) that supervises either a Style D
(Class A) or Style B (Class B) circuit of dry-contact input
devices.
Features
• Built-in type identification automatically identifies this
device as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional
power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
• LED flashes green during normal operation (programmable option) and latches on steady red to indicate alarm.
The FMM-1(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1(A) can be used to replace MMX-1(A)
modules in existing systems.