General
The TR-PULL-SA is a single action pull station requiring only one motion to activate the station. The TR-PULL-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Triga series fire alarm control panels (FACPs)
INSTALLATION
The TR-PULL-SA and TR-PULL-DA can be surface mounted to an SB-I/O surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square electrical box. You can also use the optional trim ring if the station is being semi-flush mounted
COMPATIBILITY
The TR-PULL-SA and TR-PULL-DA are compatible with the following Triga Series FACPs:
• Installer can open station without causing an alarm condition
• Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition
• Key operated test and reset lock using lock plate actuator
• Key matches compatible FACP locks
• Meets ADA requirement for 5 lbs maximum pull force to active
• Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13])
• Shell, door, and handle molded from durable LEXAN ®
• Reliable analog communications for trouble-free operation
• Braille text on station handle
• Rotary address switches for fast installation
• Handle latches in down position and the word Activated appears, clearly indicating the station has been pulled
• UL Listed, including UL 38, Standard of Manually Actuated Signaling System