General
FCM-1(A) Control Module: The FCM-1(A) Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes,
speakers, etc.). Addressability allows the FCM-1(A) to be activated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
Features
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire
SLC loop. The FCM-1(A) module requires power (for horns,
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red
when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The FCM-1(A) may be used to switch 24-volt NAC power,
audio (up to 70.7 Vrms).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01– 159 for FlashScan loops,
01 – 99 for CLIP mode loops.
• Speaker, and audible/visual applications may be wired for
Class B or A (Style Y or Z).